Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 62

Advertising
background image

Publication 1794-6.5.8 - January 2010

62 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Table 4.7

Setting the Input Filter

Bits

Channel

03

02

01

00

Input 0

07

06

05

04

Input 1

11

10

09

08

Input 2

15

14

13

12

Input 3

A/D Conversion
Rate

Low Pass Filter

0

0

0

0

1200Hz

No low pass

0

0

0

1

1200Hz

100ms low pass

0

0

1

0

1200Hz

500ms low pass

0

0

1

1

1200Hz

1000ms low pass

0

1

0

0

600Hz

No low pass

0

1

0

1

600Hz

100ms low pass

0

1

1

0

600Hz

500ms low pass

0

1

1

1

600Hz

1000ms low pass

1

0

0

0

300Hz

No low pass

1

0

0

1

300Hz

100ms low pass

1

0

1

0

300Hz

500ms low pass

1

0

1

1

300Hz

1000ms low pass

1

1

0

0

150Hz

No low pass

1

1

0

1

150Hz

100ms low pass

1

1

1

0

150Hz

500ms low pass

1

1

1

1

150Hz

1000ms low pass

Table 4.8

Configuring Your Input Module

Input Channel Configuration

03 02 01 00 Set these bits for Channel 0

07 06 05 04 Set these bits for Channel 1

11 10 09 08 Set these bits for Channel 2

15 14 13 12 Set these bits for Channel 3