Input data behavior upon module removal – Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 103

Advertising
background image

Publication 1794-6.5.8 - January 2010

Input, Output, Status and Configuration Files for Analog Modules when used with ControlNet 103

Input Data Behavior Upon
Module Removal

I/O module input data sent by the adapter upon module removal is
configurable. The adapter can:

reset the module output data to zero (reset)

leave the module output data in the last state before module
removal (hold last state)

4 Input Isolated Analog Module (Cat. No. 1794-IF4I, 1794-IF4IXT,
1794-IF4ICFXT) Table Mapping

Set EN bit Off (0) for Configuration block. Module actions (Reset, Safe
State and Hold Last State) are set using programming software.

To find the image table for:

See page:

4 Input Isolated Analog Module (Cat. No. 1794-IF4I)

103

4 Output Isolated Analog Module (1794-OF4I)

108

Isolated Analog Combo Module (1794-IF2XOF2I)

113

Table 6.1 Input Map

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Word 0

Analog Value Channel 0

Word 1

Analog Value Channel 1

Word 2

Analog Value Channel 2

Word 3

Analog Value Channel 3

Word 4

Real Time Sample

Word 5

PU

FP

CF

0

Reserved

0

0

0

0

0

BD

DN

0

Word 6

0

0

0

0

0

0

0

0

V3

V2

V1

V0

U3

U2

U1

U0

Where :

PU = Power up inconfigured

FP = Field power off

CF = In configuration mode

BD = Bad calibration

DN = Calibration accepted

U = Underrange for specified channel

V = Overrange for specified channel