Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual
Page 108

Publication 1794-6.5.8 - January 2010
108 Input, Output, Status and Configuration Files for Analog Modules when used with ControlNet
Table 6.3
Word/Bit Descriptions for Isolated Analog Input Module
Word
Decimal Bit
(Octal Bit)
Definition
Table 6.4
Setting the Input Filter
Bits
Channel
03
02
01
00
Input 0
07
06
05
04
Input 1
11
10
09
08
Input 2
15
14
13
12
Input 3
A/D Conversion
Rate
Low Pass Filter
0
0
0
0
1200Hz
No low pass
0
0
0
1
1200Hz
100ms low pass
0
0
1
0
1200Hz
500ms low pass
0
0
1
1
1200Hz
1000ms low pass
0
1
0
0
600Hz
No low pass
0
1
0
1
600Hz
100ms low pass
0
1
1
0
600Hz
500ms low pass
0
1
1
1
600Hz
1000ms low pass
1
0
0
0
300Hz
No low pass
1
0
0
1
300Hz
100ms low pass
1
0
1
0
300Hz
500ms low pass
1
0
1
1
300Hz
1000ms low pass
1
1
0
0
150Hz
No low pass
1
1
0
1
150Hz
100ms low pass
1
1
1
0
150Hz
500ms low pass
1
1
1
1
150Hz
1000ms low pass
Table 6.5
Configuring Your Input Module
Input Channel Configuration
03
02
01
00
Set these bits for Channel 0
07
06
05
04
Set these bits for Channel 1
11
10
09
08
Set these bits for Channel 2
15
14
13
12
Set these bits for Channel 3