Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 74

Advertising
background image

Publication 1794-6.5.8 - January 2010

74 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Table 4.19

Configuring Your Outputs for the 1794-IF2XOF2I Analog Combo Module

Configuration
Bits

Nominal
Range

Data Type

Output Values

(1)

Update
Rate

MSD

LSD

Hexadecimal

Decimal

0

0

0

1

4-20mA

2’s complement

<0000–7878>

<0000–30840>

5.0ms

0

0

1

0

±10V

2’s complement

<8618–79E8>

<–31208–31208> 2.5ms

0

0

1

1

±5V

2’s complement

<8618–79E8>

<–31208–31208> 2.5ms

0

1

0

0

0-20mA

2’s complement %

0–2710>

0–10000>

5.0ms

0

1

0

1

4-20mA

2’s complement %

<0–2710>

<0–10000>

5.0ms

0

1

1

0

0-10V

2’s complement %

0–2710>

0–10000>

5.0ms

0

1

1

1

±10V

2’s complement %

<–D8F0–2710>

<–10000–10000> 5.0ms

1

0

0

0

0-20mA

binary

0000–F3CF>

0000–62415>

2.5ms

1

0

0

1

4-20mA

binary

0000–F0F1>

0000–61681>

5.0ms

1

0

1

0

0–10V

binary

0000–F3CF>

0000–62415>

2.5ms

1

0

1

1

0-5V

binary

0000–F3CF>

0000–62415>

2.5ms

1

1

0

0

±20mA

offset binary

8000–F9E8>

32768–63976>

2.5ms

1

1

0

1

4-20mA

offset binary

<8000–F878>

<32768–63608>

5.0ms

1

1

1

0

±10V

offset binary

<0618–F9E8>

<1560–63976>

2.5ms

1

1

1

1

±5V

offset binary

<0618–F9E8>

<1560–63976>

2.5ms

(1)

< and > indicate the overrun beyond actual range (about 5%).

Table 4.20

Word/Bit Descriptions for the 1794-IF2XOF2I Analog Combo

Module Write

Write Word

Decimal Bit
(Octal Bit)

Definition

Word 0

Bits 00–14
(00–16)

Not used

Bit 13–14 (15–16) Safe State Source bits (S1/S0). – When EN is 0, these bits designate the source of

the safe state data.
Bit 13 = 0, bit 14 = 1 – reset outputs to 0V/0mA (used with 1794-ASB/C)
Bit 13 = 1, bit 14 = 1 – hold output at its current level (used with 1794-ASB/C)
Bit 13 = 0; bit 14 = 0 – Safe state data is in output data words

Bit 15 (17)

Output enable bit (EN). – When set (1), the outputs are enabled. This bit must be set
in order for the real time data to appear at the outputs. If this bit is not set (0), the
outputs will be determined by S1/S0.

Word 1

Bits 00–15
(00–17)

Output Channel 0 data. Refer to Table 4.19.

Advertising