60 Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Table 4.5

Analog Input Module (1794-IF4I) Write Configuration Block

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Word 0

EN

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Word 1

Chnl 3 Filter

Chnl 2 Filter

Chnl 1 Filter

Chnl 0 Filter

Word 2

Chnl 3 Configuration

Chnl 2 Configuration

Chnl 1 Configuration

Chnl 0 Configuration

Word 3

0

Real Time Sample Programmed Interval

Word 4

IC

1

TR

IT

0

0

0

0

RV

QK

CK

GO

Channel Number

Where:
EN = Not used on the 1794-IF4I.
IC = Initiate configuration bit
TR = Transparent bit
IT = Interrupt Toggle bit
RV = Revert to defaults bit
QK = Quick calibration
CK = Calibration clock
GO = Gain offset select

Table 4.6

Word/Bit Descriptions for the 1794-IF4I Analog Input ModuleWrite

Write Word

Decimal Bit (Octal
Bit)

Definition

Word 0

Bits 00–14 (00–16)

Not used. Set to 0.

Bit 15 (17)

Output enable bit (EN). – Not used in the 1794-IF4I module.

Word 1

Channels 0 through 3 Filter Selections (refer to Table 4.7 )

Bits 00–03

Channel 0 Filter Setting

Bits 04–07

Channel 1 Filter Setting

Bits 08–11 (10–13)

Channel 2 Filter Setting

Bits 12–15 (14–17)

Channel 3 Filter Setting

Word 2

Channel Configuration (refer to Table 4.B )

Bits 00–03

Channel 0 Configuration

Bits 04–07

Channel 1 Configuration

Bits 08–11 (10–13)

Channel 2 Configuration

Bits 12–15 (14–17)

Channel 3 Configuration

Word 3

Bits 00–14 (00–16)

Real Time Sample Interval – Programs the interval of the real time sample. Can be varied
from 0 to 30 seconds (30000 decimal). Resolution is in ms with granularity in 5ms steps.

Bit 15 (17)

Not used. Set to 0.