Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual
Page 75
![background image](/manuals/579281/75/background.png)
Publication 1794-6.5.8 - January 2010
Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 75
Word 2
Bits 00–15
(00–17)
Output Channel 1 data. Refer to Table 4.19.
Word 3
Input Channels 0 and 1 Filter Selections (refer to Table 4.16)
Bits 00–01
Channel 0 Filter Setting
Bits 04–07
Channel 1 Filter Setting
Word 4
Channel configuration
Bits 00–03
Input Channel 0 Configuration – Refer to Table 4.15.
Bits 04–07
Input Channel 1 Configuration – Refer to Table 4.15.
Bits 08–11
(10–13)
Output Channel 0 Configuration – Refer to Table 4.19.
Bits 12–15
(14–17)
Output Channel 1 Configuration – Refer to Table 4.19.
Word 5
Bits 00–14
(00–16)
Real Time Sample Interval – Programs the interval of the real time sample. Can be
varied from 0 to 30 seconds (30000 decimal). Resolution is in ms with granularity in 5ms
steps. (see page 4-55)
Table 4.20
Word/Bit Descriptions for the 1794-IF2XOF2I Analog Combo
Module Write
Write Word
Decimal Bit
(Octal Bit)
Definition