Scaling inputs – Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 133

Advertising
background image

Publication 1794-6.5.8 - January 2010

Calibrating Your Module 131

Scaling Inputs

Inputs are scaled using the y = mx + b linear formula, as illustrated by
the three types below.

The gain, m, and offset, b, coefficients are calculated as follows:

m = Desired Range / Input Range

b = Desired value when input returns zero (type 1 & 2)

b = – m(

Δ

x) + ( bottom of Desired Range ) (type 3)

Configu-
ration

Nominal
Range

Data Type

Scale
Figure

Output
Range

Δ

X

1

4–20mA

signed 2’s complement

Type 2

30840

NA

2

+10V

signed 2’s complement

Type 1

63938

NA

3

+5V

signed 2’s complement

Type 1

62416

NA

4

0–20mA

signed 2’s complement %

Type 2

10000

NA

5

4-20mA

signed 2’s complement %

Type 2

10000

NA

6

0–10V

signed 2’s complement %

Type 2

10000

NA

7

+10V

signed 2’s complement %

Type 1

20000

NA

8

0–20mA

binary

Type 2

62415

NA

9

4–20mA

binary

Type 2

61681

NA

A

0–10V

binary

Type 2

63938

NA

B

0–5V

binary

Type 2

62415

NA

C

+20mA

offset binary

Type 3

62416

1560

D

4–20mA

offset binary

Type 3

30840

32768

E

+10V

offset binary

Type 3

63938

799

F

+5V

offset binary

Type 3

62416

1560