Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 69

Advertising
background image

Publication 1794-6.5.8 - January 2010

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 69

2 Input/2 Output Analog Combo Module (Cat. No. 1794-IF2XOF2I)

Module Image

I/O Image

Input Data Channel 0

Input Data Channel 1

Read Back Output Data Channel 0

Read Back Output Data Channel 1

Output Data Channel 0

Output Data Channel 1

Input Size

Output Size

0 to 7 Words

0 to 7 Words

Read

Write

Real Time Sample

PU FP CF

BD DN

V1 V0

U1 U0

W1 W0

P1 P0

Set to 0

EN S1 S0

Channel Configuration

Real Time Sample Programmed Interval

IC

RV QK CK GO

Channel #

1

Channel Filters

Q0

Q1

TR IT

Table 4.14

Analog Combo Module (1794-IF2XOF2I) Read

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word 0

Input Data Channel 0

Word 1

Input Data Channel 1

Word 2

Read Back Output Channel 0

Word 3

Read Back Output Channel 1

Word 4

0

Real Time Sample

Advertising