Calibrating Your Module 123

5. Send another BTW to the module to reset the CK bit (0). When

the GO bit is low, the previously determined offset coefficients
are stored in EEPROM for the selected channels. If QK is set (1)
high, the same coefficients will be stored to all “like”
configurations (i.e. if configuration bits are set for a specific
voltage, both unipolar/bipolar, x1/x2 – will have the same
coefficients stored – see Table 7.1). If calibrate for 0-20mA
current range, 4-20mA range channels are also automatically
calibrated.

6. Monitor the module block transfer read word. Clear the IC bit to

0, and offset calibration is terminated.

Table 7.1

Configuration

Nominal Range

Data Type

Comments

4

0–20mA

signed 2’s complement
%

If you calibrate any of
this group, the rest of
the group will also be
calibrated.

8

0–20mA

binary

C

±20mA

offset binary

6

0–10V

signed 2’s complement
%

If you calibrate any of
this group, the rest of
the group will also be
calibrated.

A

0–10V

binary

B

0–5V

binary

2

±10V

signed 2’s complement

If you calibrate any of
this group, the rest of
the group will also be
calibrated.

7

±10V

signed 2’s complement
%

E

±10V

offset binary

3

±5V

signed 2’s complement

If you calibrate any of
this group, the rest of
the group will also be
calibrated.

F

±5V

offset binary

1

4–20mA

signed 2’s complement

If you calibrate 0-20mA
range, all 4- mA g s are
calibrated.

5

4-20mA

signed 2’s complement
%

9

4–20mA

binary

D

4–20mA

offset binary

Advertising