Slc-5 programming, Plc-2 programming, More – Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 38

Advertising
background image

Publication 1794-6.5.8 - January 2010

38 Module Programming

Figure 1.6

PLC-5 Family Sample Program Structure for the 1794-IF2XOF2I

PLC-2 Programming

The 1794 analog I/O modules are not recommended for use with
PLC-2 family programmable controllers due to the number of digits
needed for high resolution.

SLC-5 Programming

The SLC-5 programs (using the 1747-SN scanner) follow the same
logic as the PLC-5 family programs in the previous examples.
Differences occur in the implementation of block transfers due to the
use of “M” files in the SLC system.

Configuration data for the FLEX I/O isolated analog modules and the
1747-SN scanner must be in place before executing the following
programs. Chapter 4 contains information on the isolated analog
module configurations.

For more information on using the 1747-SN scanner module and
block transfer programming, refer to publication 1747-6.6, “Remote
I/O Scanner User Manual.”

BTR Enable Bit

EN

DN

BTW Enable Bit

1

3

ER

EN

DN

ER

BTR

BLOCK TRANSFER READ

RACK:
GROUP:
MODULE:

DATA FILE:
LENGTH:
CONTINUOUS:

N

BTW

BLOCK TRANSFER WRITE

RACK:

GROUP:
MODULE:

LENGTH:
CONTINUOUS:

N

2
3
0

N16:10

7

2

3
0

7

Program

Action

CONTROL:

N17:10

DATA FILE:

N16:50

CONTROL:

N17:0

N17:0

15

N17:10

15

Thereafter, the program continuously
performs read block transfers and write block
transfers.

2

14

N16:15

15

13

Power-up Bit

FP Bit

CF Bit

15

IC Bit

N16:56

N16:15

N16:15

Then it initiates a block transfer write to
configure the module and send data
values.

This rung toggles the Initate Configuration
bit from 0 to 1 to 0

At power-up in RUN mode, or when the
processor is switched from PROG to RUN,
the user program enables a block transfer
read.

L

14

N16:56

THIS BIT MUST BE 1

More