Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 63

Advertising
background image

Publication 1794-6.5.8 - January 2010

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter 63

Bit Settings

Input
Values

Data Format

% Underrange
%Overrange

Input Range

(2)

Module Update
Rate

Hexadecimal

Decimal

(RTSI =
0)

(RTSI =
0)
IT = 1

0

0

0

0

Channel not configured

0

0

0

1

4–20mA

signed 2’s complement

4% Under; 4%
Over

<0000–7878>

<0000–30840>

7.5ms

5.0ms

0

0

1

0

±10V

signed 2’s complement

2% Under, 2%
Over

<831F–7CE1>

<–31969–
31969>

2.5ms

2.5ms

0

0

1

1

±5V

signed 2’s complement

4% Under, 4%
Over

<8618–79E8>

<–31208–
31208>

2.5ms

2.5ms

0

1

0

0

0–20mA

signed 2’s complement
%

0% Under, 4%
Over

0–2710>

0–10000>

7.5ms

5.0ms

0

1

0

1

4-20mA

signed 2’s complement
%

4% Under, 4%
Over

<0–2710>

<0–10000>

7.5ms

5.0ms

0

1

1

0

0–10V

signed 2’s complement
%

0% Under, 2%
Over

0–2710>

0–10000>

5.0ms

5.0ms

0

1

1

1

±10V

signed 2’s complement
%

2% Under, 2%
Over

<–D8F0–2710> <–10000–

10000>

5.0ms

5.0ms

1

0

0

0

0–20mA

binary

0% Under, 4%
Over

0000–F3CF>

0000–62415>

2.5ms

2.5ms

1

0

0

1

4–
20mA

(1)

binary

4% Under, 4%
Over

0000–F0F1>

0000–61681>

7.5ms

5.0ms

1

0

1

0

0–10V

binary

0% Under, 2%
Over

0000–F9C2>

0000–63938>

2.5ms

2.5ms

1

0

1

1

0–5V

binary

0% Under, 4%
Over

0000–F3CF>

0000–62415>

2.5ms

2.5ms

1

1

0

0

±20mA

offset binary, 8000H =
0mA

4% Under, 4%
Over

<0618–F9E8>

<1560–63976>

2.5ms

2.5ms

1

1

0

1

4–20mA

offset binary, 8000H =
4mA

4% Under, 4%
Over

<8000–F878>

<32768–63608> 7.5ms

5.0ms

1

1

1

0

±10V

offset binary, 8000H =
0V

2% Under, 2%
Over

<031F–FCE1>

<799–64737>

2.5ms

2.5ms

1

1

1

1

±5V

offset binary, 8000H =
0V

4% Under, 4%
Over

<0618–F9E8>

<1560–63976>

2.5ms

2.5ms

(1)

Underrange for 4-20mA occurs in the blind area below 0 (3.2mA).

(2)

< and > indicate the overrun beyond actual range (about 5%).

Table 4.8

Configuring Your Input Module