104 Input, Output, Status and Configuration Files for Analog Modules when used with ControlNet

Table 6.2 Output (Configuration) Map

Dec.

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Oct.

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Word 0

EN

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Word 1

Channel 3 Filter

Channel 2 Filter

Channel 1 Filter

Channel 0 Filter

Word 2

Ch 3 Configuration

Ch 2 Configuration

Ch 1 Configuration

Ch 0 Configuration

Word 3

0

Real Time Sample Interval

Word 4

IC

1

TR

IT

0

CH

SK

FS

RV

QK

CK

GO

Channel Number

Word 5

Reserved

Where :

EN = Enable bit (not used on input module)

IC = Initiate Configuration bit

TR = Transparent bit

IT = Interrupt toggle bit

CH - Chop Mode Disable.

SK = FIR Filter Disable

FS = Fast Step Response

RV = Revert to default bit

QK = Quick calibration

CK = Calibration clock

GO = Gain Offset select

Table 6.3

Word/Bit Descriptions for Isolated Analog Input Module

Word

Decimal Bit
(Octal Bit)

Definition

Input Word 0

Bits 00-15
(00-17)

Channel 0 analog data – Real time input data per your configuration

Word 1

Bits 00-15
(00-17)

Channel 1 analog data – Real time input data per your configuration

Word 2

Bits 00-15
(00-17)

Channel 2 analog data – Real time input data per your configuration

Word 3

Bits 00-15
(00-17)

Channel 3 analog data – Real time input data per your configuration

Word 4

Bits 00-15
(00-17)

Real Time Sample. The elapsed time in increments programmed by the real time
sample interval.

Advertising