Tools and equipment – Rockwell Automation 1794-IF4I, -OF4I, IF2XOF2I, -IF4IXT, -IF4ICFXT, -OF4IXT, IF2XOF2IXT FLEX I/O Isolated Analog Modules User Manual

Page 122

Advertising
background image

Publication 1794-6.5.8 - January 2010

120 Calibrating Your Module

Tools and Equipment

In order to calibrate your input module you will need the following
tools and equipment:

Figure 7.1

Calibration Set-Ups

Tool or Equipment

Description

Model/Type

Available From:

Precision Voltage/Current
Source

0–10.25V, 10

μ

V resolution

or better
0–21mA, 100nA or better

HP3245A or equivalent

Precision Voltage/Current
Meter

0–10.5V, 10

μ

V or better

0–22mA, 100nA or better

Datron, Wavetek or
equivalent

Industrial Terminal and
Interconnect Cable

Programming terminal for
A–B family processors

Cat. No. 1770–T3 or Cat.
No. 1784–T45, –T47, –T50,
etc.

Allen–Bradley Company
Highland Heights, OH

ATTENTION

The isolated analog modules are shipped already
calibrated for 150Hz, 300Hz and 600Hz.
No
recalibration is required when switching between
these conversion rates.

1794-TB2, -TB3

0 ±15

34±51

16±33

A

B

C

Precision Voltage Source

Using a Precision V oltage Source

These terminals not on 1794-TB2

1794-TB2, -TB3

0 ±15

34±51

16±33

A

B

C

Precision Current Source

Using a Precision Current Source

These terminals not on 1794-TB2

Signal

Ret

Signal

Ret

Advertising