Local Mode

Remote Mode

The valid range of slave addresses on a half-duplex network is 000

through 376 octal (000 through 254 decimal) accommodating a total of
255 devices. The valid range of addresses on a DH-485 network is 00
through 37 octal (00 through 31 decimal).

To let addressing of up to 255 DH-485 nodes, eight groups (group
numbers 00 through 07) of DH-485 networks are established. Each
group number defines a DH-485 network, which can consist of up to
32 nodes each (except for group 07 which is limited to 31 nodes).

Refer to the table on page 3-6.

During configuration of the interface module, the module’s group
number is selected if Remote mode has been selected.

In remote mode, the module appears transparent to the half-duplex
master, so that remote SLC 500 controllers can be polled directly as
individual slaves on the half-duplex network. The interface module
responds to the half-duplex master if the station address specified
corresponds to the node address of any (token-passing) station on
the DH-485 network connected to that interface module.

SLC 500
Node 02

SLC 500
Node 01

SLC 500
Node 03

SLC 500
Node 00

PLC 5
controller

DF1 Master

RS-232C DF1

DH-485

DH-485

Link Coupler
((1747-AIC)

Link Coupler
((1747-AIC)

Link Coupler
((1747-AIC)