Slc output file to the interface module, Modem init string for characters 1 through 14 -14, Modem init string for characters 1 through 14 – Rockwell Automation 1747-KE,D17476.12 DH-485/RS-232C Interface Module User Manual
Page 80

Publication 1747-UM005B-EN-P - March 2006
6-14 Module Configuration Using the Backplane
Modem Init String for Characters 1 Through 14
To set up string characters 1 to 14, build the configuration in the table
shown below. Please note that sending a ~ character produces a one
second wait on the modem.
Follow the configuration instructions found on page 6-2.
SLC Output File to the Interface Module
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
(1)
Module
Mode
Bit
Data
Hand
shake
Bit
Read or
write
Bit
Reset
Interface
Module
Bit
Reserved
Data ID=4
1
1st ASCII character
2nd ASCII character
2
3rd ASCII character
4th ASCII character
3
5th ASCII character
6th ASCII character
4
7th ASCII character
8th ASCII character
5
9th ASCII character
10th ASCII character
6
11th ASCII character
12th ASCII character
7
13th ASCII character
14th ASCII character
(1)
The output status word is defined on page 6-6. To configure the Modem Init String, the Read or Write Bit must be at 0 and the Module Mode Bit must be
at 1. To read the Modem Init String, the Read or Write Bit must be 1 and the Module Mode Bit can be either 0 or 1.