Publication 1747-UM005B-EN-P - March 2006

3-8 Communicate with the Interface Module

The group number is used by the interface module to create a
half-duplex DF1 address for each node on the DH-485 network. The
DF1 addresses are the octal equivalent of an eight bit binary word
with the three most significant bits corresponding to the group
number and the five least significant bits corresponding to the local
network address.

Addresses

The following table lists the devices from the above network along
with their DH-485 local network address and their DF1 multi-drop
address.

Devices and Corresponding Addresses

011

11101

01 111 101

1

7

5

Group Number
(3 in this example)

DH-485 Local Network Address
(29 in this example)

and

combine to make
this binary word

which has this octal value.
(DF1 Multi-drop Address)

Group Device

DH-485 Address
(decimal)

DF1 Address
(binary)

DF1 Address
(octal equivalent)

00

1747–KE

01

00|000|001

001

SLC 500

02

00|000|010

002

SLC 500

05

00|000|101

005

SLC 500

09

00|001|001

011

01

1747–KE

00

00|100|000

040

SLC 500

04

00|100|100

044

SLC 500

03

00|100|011

043

1747–KE

01

01|000|001

101

02

SLC 500

00

01|000|000

100

SLC 500

25

01|011|001

131

SLC 500

16

01|010|000

120

SLC 500

04

01|000|100

104