Slc output file to the interface module, Modem init string for characters 15 through 28 -15, Modem init string for characters 15 through 28 – Rockwell Automation 1747-KE,D17476.12 DH-485/RS-232C Interface Module User Manual

Page 81

Advertising
background image

Publication 1747-UM005B-EN-P - March 2006

Module Configuration Using the Backplane 6-15

Modem Init String for Characters 15 Through 28

Build the configuration in the table shown below if you need to use
characters 15 to 28 of the Modem Init String. Please note that sending
a ~ character produces a one second wait on the modem.

SLC Output File to the Interface Module

Bit

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

(1)

Module
Mode
Bit

Data
Hand
shake
Bit

Read or
Write
Bit

Reset
Interface
Module
Bit

Reserved

Data ID=5

1

15th ASCII character

16th ASCII character

2

17th ASCII character

18th ASCII character

3

19th ASCII character

20th ASCII character

4

21st ASCII character

22nd ASCII character

5

23rd ASCII character

24th ASCII character

6

25th ASCII character

26th ASCII character

7

27th ASCII character

28th ASCII character

(1)

The output status word is defined on page 6-6. To configure the Modem Init String, the Read or Write Bit must be at 0 and the Module Mode Bit must be
at 1. To read the Modem Init String, the Read or Write Bit must be 1 and the Module Mode Bit can be either 0 or 1.