Slc output file to the interface module, Modem init string for characters 15 through 28 -15, Modem init string for characters 15 through 28 – Rockwell Automation 1747-KE,D17476.12 DH-485/RS-232C Interface Module User Manual
Page 81

Publication 1747-UM005B-EN-P - March 2006
Module Configuration Using the Backplane 6-15
Modem Init String for Characters 15 Through 28
Build the configuration in the table shown below if you need to use
characters 15 to 28 of the Modem Init String. Please note that sending
a ~ character produces a one second wait on the modem.
SLC Output File to the Interface Module
Bit
Word
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
0
(1)
Module
Mode
Bit
Data
Hand
shake
Bit
Read or
Write
Bit
Reset
Interface
Module
Bit
Reserved
Data ID=5
1
15th ASCII character
16th ASCII character
2
17th ASCII character
18th ASCII character
3
19th ASCII character
20th ASCII character
4
21st ASCII character
22nd ASCII character
5
23rd ASCII character
24th ASCII character
6
25th ASCII character
26th ASCII character
7
27th ASCII character
28th ASCII character
(1)
The output status word is defined on page 6-6. To configure the Modem Init String, the Read or Write Bit must be at 0 and the Module Mode Bit must be
at 1. To read the Modem Init String, the Read or Write Bit must be 1 and the Module Mode Bit can be either 0 or 1.