Publication 1747-UM005B-EN-P - March 2006

4-4 Installation and System Configuration

Set the Module’s Mode

Setting the module’s mode depends on which method you want to
use to configure the module. You can configure the module using:

• an ASCII terminal.
• backplane communications.

Decide which method you want to use and then place the JW4 jumper
according to the directions given below.

Configure with an ASCII Terminal

Configuration of the interface module with an ASCII terminal is
allowed only when the JW4 jumper is in Configuration mode. Place
the module in the Configuration mode that corresponds to the
functionality you chose for the interface module.

JW4 in Configuration Mode

Configure Through the Backplane

Reading and writing configuration data through the backplane is
allowed only for series B interface modules, and then only when the
JW4 jumper is in the vertical Run mode position. Place the module in
vertical Run mode.

JW4 in Vertical Run Mode

IMPORTANT

You can only use backplane communications if you
selected series B functionality for the module.

Horizontal

Configuration

Mode

Vertical

Configuration

Mode

Series A Functionality

Series B Functionality

JW4

Vertical Run Mode