6-4 Module Configuration Using the Backplane
Place the Module into
Software Run Mode from
SLC Processor
When configuration is complete, place the module in software Run
mode by following these steps.
Place the Module in Run Mode
With the SLC processor you
The interface module then
1. Reset the Module Mode bit to
software Run (O:e.0/15).
2. Set the Data Handshake bit to
indicate the data in the Output
Image file is valid (O:e.0/14).
3. Resets the Module Mode bit to
software Run in the SLC Input
Image File (I:e.0/15).
4. Sets the Data Handshake bit
(I:e.0/14).
5. Reset the Data Handshake bit
(O:e.0/14).
6. Resets the Data Handshake bit
(I:e.0/14).