Place the module in run mode, Place the module into software run mode from – Rockwell Automation 1747-KE,D17476.12 DH-485/RS-232C Interface Module User Manual

Page 70

Advertising
background image

Publication 1747-UM005B-EN-P - March 2006

6-4 Module Configuration Using the Backplane

Place the Module into
Software Run Mode from
SLC Processor

When configuration is complete, place the module in software Run
mode by following these steps.

Place the Module in Run Mode

With the SLC processor you

The interface module then

1. Reset the Module Mode bit to

software Run (O:e.0/15).

2. Set the Data Handshake bit to

indicate the data in the Output
Image file is valid (O:e.0/14).

3. Resets the Module Mode bit to

software Run in the SLC Input
Image File (I:e.0/15).

4. Sets the Data Handshake bit

(I:e.0/14).

5. Reset the Data Handshake bit

(O:e.0/14).

6. Resets the Data Handshake bit

(I:e.0/14).

Advertising