7-2 Interpret the LED Indicators

Shown below are possible error conditions represented by the LED
indicators and their possible solutions.

LED Indicator Error Conditions

Input Image Description

Shown below is the input image that provides status to the SLC
processor. Bit 13 indicates the battery status. The status information
contained in bit 13 corresponds to the module’s BA LOW LED
indicator. Bit 15 indicates whether the module requires configuration
or not.

Input Image

LED

Color

Status

Condition

Solution

ACT

Green

Flashing The module requires configuration. The module requires configuration.

OFF

The module is not receiving power
from the backplane. A fault
condition exists.

Check the SLC power supply. Make
sure the interface module is
properly installed in the rack.

485

Green

OFF

The DH485 port is not active for
communication.

Check DH-485 cabling. Make sure
the module’s JW4 jumper is not in
Configuration mode.

DF1

Green

OFF

DF1 host is transmitting data and
LED indicator is not flashing.

Check DF1 cabling. Make sure the
module’s JW4 jumper is not in
Configuration mode.

FAULT

Red

ON

A system problem was detected
during background diagnostics.

Contact your Allen-Bradley
representative.

BA LOW Red

ON

The voltage of the battery that
backs up configuration RAM is low.

Replace battery.

CFG

Green

OFF

The CONFIG port is transmitting
data and LED indicator is not
flashing.

Check ASCII terminal cabling. Make
sure the module’s JW4 jumper is in
Configuration mode.

1 = Acknowledges that the module
was reset from the SLC processor.

0 = Module is running.
1 = Module requires configuring or is
in software Configuration mode.

Status Word, Word 0

B

it Number (decimal) 15 14 13 12 11 10 9

8 7

6

5

4

3

2

1

0

I:e.0

0 = Battery is good.
1 = Battery is low.

0 = Modem carrier detected.
1 = Modem carrier inactive
(no modem connected).

0 = Input image data may not be valid.
1 = SLC output image data is accepted by the
interface module. Input image data is valid.

Reset Acknowledge Bit

(1)

Data Handshake Bit

(1)

Status Code Bits

Data ID Value Bits

(1)

(echoed from
Output Image)

Modem Lost Bit

(1)

Battery Status Bit

Module Mode Bit

(1)

Applies to series B, or later, interface modules only.