6-8 Module Configuration Using the Backplane

Build the DF1 Configuration
Packet

Use the SLC processor to set up the DF1 port.

Build the configuration packet shown by following the configuration
instructions found on page 6-2.

SLC Output File to the Interface Module


Bit
Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

(1)

Module
Mode
Bit

Data
Handshake
Bit

Read or
Write
Bit

Reset
Interface
Module Bit

Reserved

Data ID=2

1

Embedded
Response
Detect
(Full) or
Local/Rem
ote Mode
(Half)

Half or
Full-
duplex

Constant
Carrier
Detect

(2)

Hardware
Hand-
shaking

(2)

Check
sum

Duplicate
Packet
Detection

Stop
Bits

Parity

Bits per
Character

DF1
Communication
Rate

2

Modem Init String Delay (0...25 s)

Enq/Msg Retries (0...254)

3

Slave Address (Local) (0...254)
Group Number (Remote) (0...7)

Master Station Address (Half Duplex) (0...254)
NAK Rec Retries (Full Duplex) (0...254)

4

ACK/POLL Timeout (0...65,535 x 5 ms)

5

Message Timeout (100...12,750 ms)

6

RTS ON Delay (0...65,535 x 5 ms)

(3)

7

RTS OFF Delay (0...65,499 x 5 ms)

(3)

(1)

The output status word is defined on page 6-6. To configure the DF1 parameters the Read or Write Bit must be 0 and the Module Mode Bit must be 1. To read the
DF1 parameters, the Read or Write Bit must be 1 and the Module Mode Bit can either be 0 or 1.

(2)

If Constant Carrier Detect is enabled, Hardware Handshaking is forced on.

(3)

The value is ignored if full-duplex is chosen.