Publication 1747-UM005B-EN-P - March 2006

Module Configuration Using the Backplane 6-5

Read the Module’s
Configuration from the SLC
Processor

The interface module’s current configuration can be read back to the
SLC processor using the Input and Output Image files.

Read the Module’s Configuration from the SLC Processor

IMPORTANT

The interface module can be in software Run or
software Configuration mode during the read
operation.

With the SLC processor you

The interface module then

1. Set the Read or Write bit to

indicate a configuration read
operation (O:e.0/13).

2. Set the Data ID value for the

configuration parameters to be
read (O:e.0/0...3).

3. Set the Data Handshake bit to

indicate the data in the Output
Image file is valid (O:e.0/14).

4. Interprets the Data ID value.

5. Gets the configuration data from

the Interface Module.

6. Loads the data into the Input

Image file (I:e.1...7).

7. Sets the Data Handshake bit to

indicate the image data is valid
(I:e.0/14).

8. Read configuration data.

9. 9. Reset the Data Handshake bit

(O:e.0/14).

10. 10. Resets the Data Handshake

bit (I:e.0/14).