Dh-485 port menu, Dh-485 port setup parameters, Dh-485 port menu -7 – Rockwell Automation 1747-KE,D17476.12 DH-485/RS-232C Interface Module User Manual

Page 61: Dh-485 port setup parameters -7

Advertising
background image

Publication 1747-UM005B-EN-P - March 2006

Module Configuration Using an ASCII Terminal 5-7

DH-485 Port Menu

The DH-485 PORT Setup Menu provides six selections.

DH-485 Port Menu

DH-485 Port Setup Parameters

When the module is powered up for the first time, the DH-485 port
will be set to the default parameters. If these parameters are changed
and the setup is saved, then the module will always power up with
the new settings, unless the battery fails and power to the module’s
RAM is lost.

DH-485 Port Setup Parameters

DF1

PORT Setup Menu

1. Baudrate
2. Bits per character
3. Parity
4. Stop bits

X. SAVE AND EXIT

Enter Selection. . . . .

Parameter

Default

Options

Description

Node Address

2

0...31 (decimal)

The address of this node on the DH-485 network. Every
device on the DH-485 network must be given a unique
node address. For optimum performance, set devices to
consecutive addresses starting at 0. This minimizes the
solicitation of new stations.

Max. Node Address 31

1...31 (decimal)

The number of nodes that will be polled. For optimum
performance this value should be set no larger than the
value of the highest numbered node on the network.

Message Timeout

10,000 ms

100...12,750 ms

The time to wait for a response to a message sent on a
DH-485 network.

Pass Through

Disabled

Enabled, Disabled

Determines whether diagnostic commands are executed
by the module (Disabled) or passed through to the host
(Enabled).

Communication Rate 19200

300, 600, 1200, 2400,
4800, 9600, 19200

The speed in bits per second at which data is transferred
on the DH-485 link.
Important: All stations on the DH-485 link must be set to
the same communication rate.

Advertising