Publication 1747-UM005B-EN-P - March 2006

Interpret the LED Indicators 7-3

Status Codes from the
Module to the Processor

The module informs the SLC processor on the status of the configure
or read transaction by placing a status value in the Input Image file
word 0, bits 4 to 10. A value of 00 indicates that the status is okay.

Status Codes from the Module to the SLC Processor

SLC Fault Code

If a fault has occurred in the SLC system and the SLC fault code
indicates the slot the interface module is installed in, the fault might
be associated with the module I/O configuration. Refer to the table
below.

SLC Fault Codes

Value
(hex)

Value
(dec)

Indicates improper status for

01

01

Day

02

02

Month

03

03

Year

04

04

Day of the Week

05

05

Hour

06

06

Minute

07

07

Second

08

08

Data ID

09

09

(Not Used)

0A

10

(Not Used)

0B

11

DF1 Enq/Msg Retry

0C

12

Modem Init String Delay

0D

13

Master Station/NAK Rec Retry

0E

14

Slave Address/Group Number

0F

15

(Not Used)

10

16

DF1 Message Timeout

11

17

(Not Used)

12

18

RTS Off Delay

13

19

DH-485 Node Address

14

20

DH-485 Max Node Address

15

21

DH-485 Communication Rate

16

22

DH-485 Message TImeout

17

23

Modem Init String character

18

24

A write operation is attempted, but the configuration bit is not
set (still in software Run mode).

SLC Fault Code (S:6)

Possible Reason

xx54

(1)

(1)

xx refers to the slot where the module is installed.

Wrong ID code was entered.

xx55

(1)

Wrong ID code was entered or wrong input and output
size were entered.