6-16 Module Configuration Using the Backplane

Use the Real Time Clock

You can use the interface module as a Real Time Clock in conjunction
with normal module operation.

Set up the Calendar/Clock Function by using the configuration
instructions found on page 6-2 and the configuration packet
information shown below.

SLC Output Status to the Interface Module

Bit

Word

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

0

(1)

Module
Mode
Bit

Data
Hand
shake
Bit

Read
or
Write
Bit

Reset
Interface
Module
Bit

Reserved

Data ID=1

1

Day (1...31)

2

Month (1...12)

3

Year (00...99)

4

Day of the Week (1...7, where Sunday=1 and Saturday=7)

5

Hour (0...23 [only 24 hour clock is available])

6

Minute (0...59)

7

Second (0...59)

(1)

The output status word is defined on page 6-6. To set the Real Time Clock, the Read or Write Bit must be 1. To read the Real Time Clock, the Read or Write
Bit must be 1 and the Module Mode Bit can either be at 0 or 1.