8-2 Application Examples

Parameter Settings

For this example, configure the parameters to the settings provided
below.

DF1 Configuration (N10:11...17)

DH-485 Configuration (N10:21...27)

Modem Init String Characters 1-14 (N10:31-37)

c d e f g h i j k l m n o p

Modem Init String Characters 15-28 (N10:41-47)

A B C (null)

Parameter

Configuration

Word and Bits Used

Communication Rate

1200

N10:11/0...2

Bits Per Character

8

N10:11/3

Parity

None

N10:11/4...5

Stop Bits

1

N10:11/6

Duplicate Packet Detection

Disabled

N10:11/7

Checksum

BCC

N10:11/8

Hardware Handshaking

Disabled

N10:11/9

Constant Carrier Detect

Disabled

N10:11/10

Duplex Setting

Full

N10:11/11

Embedded Response Detect

ADER

N10:11/12

ENQuiry Retries

2

N10:12/0...7

Modem Init String Delay

5 s

N10:12/8...15

NAK Received Retries

4

N10:13/0...7

DF1 Slave Address

(1)

(1)

Not applicable for full-duplex.

7

N10:13/8...15

ACK Timeout

37 x 5 ms

N10:14/0...15

Message Timeout

100 ms

N10:15/0...15

RTS On Delay

(1)

5 x 5 ms

N10:16/0...15

RTS Off Delay

(1)

7 x 5 ms

N10:17/0...15

Parameter

Configuration

Word and Bits
Used

Node Address

5

N10:21/0...7

Max Node Address

31

N10:21/8...15

Communication Rate

19,200

N10:22/0...3

Pass Through

Enabled

N10:22/4

Message Timeout

12000 ms

N10:23/0...15