Configure the Module From the SLC Processor

With the SLC processor you

The interface module then

1. Place the module into software

Configuration mode, if it is not
already. Do this setting the
Module Mode Bit (O:e.0/15).

2. Load the correct Data ID value

for the parameters you will
configure (O:e.0/0...3).

3. Build the Output Image file with

configuration data (O:e.1...7).

4. Write the configuration data by

resetting the Read or Write bit
(O:e.0/13).

5. Set the Data Handshake bit to

indicate the data in the Output
Image file is valid (O:e.0/14).

6. Gets the configuration data from

the SLC Output file.

7. Configures parameters on the

Interface Module.

8. Echoes the Data ID (I:e.0/0...3)

and configuration data (I:e.1...7),
and places the status of the
configuration transaction in the
SLC Input File (I:e.0/4...10).

9. Sets the Data Handshake bit to

indicate the image data is valid
(I:e.0/14).

10. Reset the Data Handshake bit

(O:e.0/14).

11. Resets the Data Handshake bit

(I:e.0/14).

12. Save your configuration changes

by putting the module in
software Run mode.

IMPORTANT

The configuration data that is loaded does not take
effect until the interface module goes to software
Run mode. Therefore, to save your configuration
changes be sure to put the module in software Run
mode.