Standalone mode – Rockwell Automation 1771-DMC_DMC1_DMC4_DXPS Control Coprocessor User Manual User Manual

Page 15

Advertising
background image

Chapter 1

Introducing the Control Coprocessor

1-5

Control coprocessor

can read/write PLCĆ5

dataĆtable and statusĆ

file information

PLCĆ5

Programmable

Controller

Control Coprocessor

User Memory

PLCĆ5 interface routines

called in a C or BASIC

program

PLCĆ5 controlĆlogic

program (MSG) initiates

communication

PLCĆ5

Programmable

Controller

Control Coprocessor

ControlĆlogic

program using

MSG instruction

Interface routines in C or

BASIC program accept,

interpret, and respond to

PLCĆ5 programmable

controller

discrete I/O read/write
block-transfer

read/write

Important:

If a fault occurs in a control coprocessor that is connected to

certain PLC-5 programmable controllers via the side connector, the
programmable controller may be unable to clear the major fault word
without first resetting the control coprocessor. In extreme cases, you may
need to separate the control coprocessor from the programmable controller.
The programmable controllers on which this may be necessary are:

PLC-5/60 (series B revision B)
PLC-5/40 (series B revision B)
PLC-5/30 (series A revision B)
PLC-5/20 (series A revision A)
PLC-5/11 (series A revision A)

Standalone Mode

In standalone mode, you do not connect the control coprocessor directly to
the PLC programmable controller. The control coprocessor can reside in
the same chassis as the programmable controller or in a remote chassis.

Programmable controller

controlĆlogic program

initiates communication

using discreteĆ and/or

blockĆtransfer read and

write instructions

Programmable Controller

Control Coprocessor

ControlĆlogic program

using discreteĆ and/or

blockĆtransfer

instructions

Interface routines in C or

BASIC program accept,

interpret, and respond to

programmable controller

The control coprocessor

can initiate directĆaccess

communication to PLCĆ5

user memory as shown here.

You do not need to program

your PLCĆ5 programmable

controller to support these

calls.

A PLCĆ5 controlĆlogic

program can initiate directĆ

access communication to

the control processor as

shown here.

A PLCĆ5 controlĆlogic

program can initiate backĆ

plane communication with

the control processor in directĆ

connect mode via:

Tip

We recommend that you

use 1Ćslot addressing for

standalone mode.

Only the programmable

controller initiates commuĆ

nication with a standalone

control coprocessor.

Communication is via the backĆ

plane using discreteĆ or blockĆ

transfer read/write instructions.