Chapter 3

Getting Started with the Control Coprocessor

3-10

Configure the Default Startup Parameters

Configure the default startup parameters of the control coprocessor using
the CC_CFG utility. See Figure 3.11.

Figure 3.11

Default Parameters for the Control Coprocessor

Welcome to PCBridge

PCBridge Microware’s PC hosted OS-9/680x0 Development System

VT100

16:05 -CA -PR -LO -LF -LE +XO -CT CD COM1 9600N81 PCBridge

$ cc_cfg -add=22 -rst=disable -tag=0

Control Coprocessor Station Address:

22 octal

PLC-5 to Control Coprocessor reset:

disabled

TAGs - Size of current TAG Table:

1024

Size requested for next boot:

0

With this utility, you:

set the control coprocessor station address

enable/disable the capability of the PLC programmable controller to

reset the control coprocessor when the PLC programmable controller
encounters a hardware fault

configure the size of the TAG table

Syntax for the CC_CFG utility is:

cc_cfg {<opts>}

functions: Configure Control Coprocessor Parameters

options:

-add=<octl num> Station Address (0-77 octal)
-rst=<str>

Enable/Disable PLCs’ reset to CC

-tag=<num>

Request size of TAG table

The station address and reset parameters take effect immediately.

The selected size of the TAG table is effective after the next system boot.
If there is insufficient memory available for the configuration, 1024 is the
default size used for 1771-DMC1 and 1771-DMC4 control coprocessors.
Zero is the default TAG-table size for the 1771-DMC control coprocessor.