API Library of Routines

Appendix B

MSG_READ_W_HANDLER

B-96

Returns

Status

Symbolic Name

Meaning

0

CC_SUCCESS

Operation successful

124

CC_E_FAIL

I/O completed with errors

133

CC_E_BAD_MSGID

Message number invalid

157

CC_E_NOTCONNECT

PLC is not connected or offline

160

CC_E_INV_TO

Invalid timeout value

162

CC_E_INV_CTYPE

Invalid coprocessor data type

163

CC_E_INV_PTYPE

Invalid PLCĆ5 data type

181

CC_E_MSGPEND

Message already pending

182

CC_E_MSG_ABORT

Message aborted

190

CC_E_SIZE

Invalid size for operation

191

CC_E_TOOSMALL

Size of buffer too small

Description

Use the MSG_READ_W_HANDLER function to handle unsolicited
message read instructions from the PLC-5 programmable controller. This
function puts an entry in the Message Control Table (MCT) for the
requested message number (0-31). When the PLC-5 programmable
controller executes that message number, data from the user-specified
buffer is transferred to the PLC-5 programmable controller.

This function is synchronous. When this function is initiated, the
application program stops until the function completes or fails. For the
asynchronous version of this command see MSG_READ_HANDLER.