Chapter 5

Developing Programs

5-9

This section defines the MSG functions that process unsolicited messages
from a PLC-5 programmable controller. See Appendix B, Application
Program Interface Routines, for more information.

Read/Write MSG Functions
Use read/write MSG functions to process unsolicited MSG instructions
from a PLC-5 ladder-logic program. See Table 5.G.

Table 5.G

ControlĆCoprocessor MSG Read/Write Processing Functions

Function

What It Does

Why You Need It

When You Use It

MSG_READ_W_HANDLER

Processes an unsolicited PLCĆ5

MSG read instruction

To perform synchronous

processing of an unsolicited

PLCĆ5 MSG read instruction

When you want to transfer read data to

the PLCĆ5 programmable controller

before the next step of the application

program is executed

MSG_READ_HANDLER

Initiates processing of an

unsolicited PLCĆ5 MSG

read instruction

To perform asynchronous

processing of an unsolicited

PLCĆ5 MSG read instruction

When you want to transfer read data to

the PLCĆ5 programmable controller but

return controlto the application program

before the message is executed (also,

see MSG_WAIT function)

MSG_WRITE_W_HANDLER Processes an unsolicited PLCĆ5

MSG write instruction

To perform synchronous

processing of an unsolicited

PLCĆ5 MSG write instruction

When you want to receive write data

from the PLCĆ5 programmable controller

before the next step of the application

program is executed

MSG_WRITE_HANDLER

Initiates processing of an

unsolicited PLCĆ5 MSG

write instruction

To perform asynchronous

processing of an unsolicited

PLCĆ5 MSG write instruction

When you want to receive write data from

the PLCĆ5 programmable controller but

return controlto the application program

before the message is executed (also,

see MSG_WAIT function)

When a PLCĆ5 programmable controller generates a Message READ instruction, a corresponding MSG_READ_HANDLER or

MSG_READ_W_HANDLER function must be used by the control coprocessor to handle the request. When a PLCĆ5 programmable controller

generates a Message WRITE instruction, a corresponding MSG_WRITE_HANDLER or MSG_WRITE_W_HANDLER function must be used by the

controlcoprocessor to handle the request.

When a PLC-5 programmable controller initiates an unsolicited read/write
MSG instruction, use read/write MSG functions in the control coprocessor
for transferring small amounts of data between the programmable
controller and the control coprocessor. The maximum size that you can
specify for the buffer in the read/write MSG function is 240 bytes for a
read and 234 bytes for a write.

For transferring larger amounts of data between the programmable
controller and the control coprocessor, use a read/write MSG function in
conjunction with a read/write DTL function in your control-coprocessor
program. You can transfer up to 1,000 words between the control
coprocessor and a PLC-5 programmable controller using the read/write
DTL function.