Rockwell Automation 1738-ADNX ArmorPoint I/O DeviceNet Adapters User Manual

Page 104

Advertising
background image

Publication 1738-UM001A-EN-P - February 2005

B-30 Quick Start For the 1738-ADNX

Notice the fields have been filled in for you.

• The 1756-DNB scanner will be receiving 12 bytes of data that

the 1738-ADNX produces.

• The 1756-DNB scanner will be outputting 3 bytes of data that

the 1738-ADNX consumes such as the 1738-OB4EM12 outputs.

Sometimes it is easy to get confused and reverse the numbers if
these values are entered manually (in this case, entering
incorrectly input size = 3 and output size = 12). It is a nice
feature that RSNetWorx for DeviceNet fills these values in for
you.

• On the main network, the 1738-ADNX is acting as an adapter so

it is producing those twelve bytes of data for the 1756-DNB. You
are now configuring the 1756-DNB, so those twelve bytes get
filled for Input Size as shown above.

16. Click Cancel to close the Edit I/O Parameters window.

Values
observed
earlier.

The values match what was observed earlier.