Rockwell Automation 1738-ADNX ArmorPoint I/O DeviceNet Adapters User Manual

Page 41

Advertising
background image

Publication 1738-UM001A-EN-P - February 2005

What Is the ArmorPoint DeviceNet Adapter? 2-25

77

Wrong Data Size

Data size expected by the device does
not match scan list entry.

Reconfigure your module for correct
transmit and receive data sizes.

78

No Such Device

Slave device in scan list table does

not exist.

Add the device to the network, or
delete scan list entry for that device.

79

Transmit Failure

Adapter has failed to transmit

a message.

Make sure that other modules exist on
the backplane.

80

In Idle Mode

Adapter is in IDLE mode.

No action necessary.

If you want the adapter to run, put it in
RUN mode.

82

Fragmentation Error

Error detected in sequence of
fragmented I/O messages

from device.

Check scan list table entry for slave
device to make sure that input and
output data lengths are correct.

Check slave device configuration.

83

Slave Init Error

Slave device is returning error
responses when scanner attempts to
communicate with it.

Check accuracy of scan list table entry.

Check slave device configuration. Slave
device might be in another master’s
scan list.

Reboot slave device.

84

Not Yet Initialized

Adapter is initializing the

DeviceNet channel.

No action.

85

Rcv Buffer Overflow

Data size is larger than 255 bytes.

Configure the device for a smaller data
size.

86

Device Went Idle

Device is producing zero length data
(idle state) while channel is in

Run Mode.

Check device configuration and slave
node status.

89

ADR Failed

Failure occurred when downloading
ADR data to the I/O module.

Reconfigure the ADR download data for
the I/O module.

91

Port Bus Off

Bus-off condition detected on
communications port.

Scanner is detecting communications
errors.

Check DeviceNet connections and
physical media integrity.

Check system for failed slave devices or
other possible sources of network
interference.

92

Port Power Off

No network power detected on
communications port.

Provide network power.

Make sure that scanner drop cable is
providing network power to adapter
communications port.

Node Status Table Numeric Code Definitions

Numeric Code:

Text Message:

Definition:

Take this action:

Advertising