6-2 Troubleshoot the ArmorPoint DeviceNet Adapter

DeviceNet Status

Off

Device is not on line:

- Device attempting to AutoBaud

- Device has not completed dup_MAC_ID test

- Device not powered - check module status indicator.

Flashing Green

Device is on line but has no connections in the established state.

Green

Device is on line and has connections in the established state.

Flashing Red

One or more I/O connection in timed-out state.

Red

Critical link failure - failed communication device. Device
detected error that prevents it from communicating on the
network. (Possible duplicate MACID or baud rate mismatch).

PointBus Status

Off

Device is not on line:

- Device has not completed dup_MAC_ID test

- Device not powered - check module status indicator.

Flashing Green

Device is on line but has no connections in the established state.

Green

Device is on line and has connections in the established state.

Flashing Red

One or more I/O connection in timed-out state.

Red

Critical link failure - failed communication device. Device
detected error that prevents it from communicating on the
network. (Possible duplicate MACID or baud rate mismatch).

Flashing Red/Green

Communication faulted device - the device has detected a
network access error and is in communication faulted state.
Device has received and accepted an Identify Communication
Faulted Request - long protocol message.

PointBus Status
(1738-ADNX only)

Off

No power applied to device.

Device not on line

Device has not completed dup_MAC_ID test.

Green

Subnet on line and has connections in the established state.

Flashing Red

Recoverable fault:

- No scanlist configured

- Problem with module in scanlist (missing, mismatch, etc.).

Red

Unrecoverable fault may require device replacement

(Possible duplicate MACID or baud rate mismatch.)

System Power

Off

Not active - Field power is off or dc-dc-converter problem.

Green

System power on - dc-dc converter active (5V).

Adapter Power

Off

Not active - Field power is off.

Green

Power on, 24V present.

Indication

Indication

Probable Cause