D-8 Default Data Maps

1738-IE2V Analog Input Module

Message size: 6 Bytes

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Produces (scanner Rx)

Input Channel 0 - High Byte

Input Channel 0 - Low Byte

Input Channel 1 - High Byte

Input Channel 1 - Low Byte

Status Byte for Channel 1

Status Byte for Channel 0

OR

UR

HHA LLA

HA

LA

CM

CF

OR

UR

HHA LLA

HA

LA

CM

CF

Consumes (scanner Tx)

No consumed data

Where: CF = Channel Fault status; 0 = no error, 1 = fault

CM = Calibration Mode; 0 = normal, 1 = calibration mode

LA = Low Alarm; 0 = no error, 1 = fault

HA = High Alarm; 0 = no error, 1 = fault

LLA = Low/Low Alarm; 0 = no error, 1 = fault

HHA = High/High Alarm; 0 = no error, 1 = fault

UR = Underrange; 0 = no error, 1 = fault

OR = Overrange; 0 = no error, 1 = fault