B-14 Quick Start For the 1738-ADNX

6. Wait for parameter 8 to return to idle. Then click the Monitor

icon to end monitoring. Notice the following:

• Parameter 1 has been filled in for you. There are three

ArmorPoint I/O modules in the backplane, causing the
default to change from 31 to 3.

• Parameter 3: Verify the Backplane Baudrate is 125 Kbaud. If it is

not, you will need to find out why and make the necessary
corrections
.

• Parameter 9, 10, 11, and 12 have been filled in for you.

Note that you do not need to view the Subnet to determine
where the data has been mapped. You can go back to monitor
mode and view parameter 14, Cycling I/O Mapping. The help for
this parameter states how to use the parameter to determine
mapping.

7. Press OK to close this window.

Expand the
column to
view all the
text.

Consume size is
data that the
adapter will
consume from
the scanner.
These are the
outputs being
sent from the
scanner to the
ArmorPoint I/O
adapter.

Produce size is
data the
1738-ADNX
adapter will
produce for the
1756-DNB
scanner. This
will be discussed
in more detail
later in this
section.