Rockwell Automation 1738-ADNX ArmorPoint I/O DeviceNet Adapters User Manual

Page 72

Advertising
background image

Publication 1738-UM001A-EN-P - February 2005

A-2 Specifications

ArmorPoint DeviceNet Adapters - 1738-ADN12, -ADN18, -ADN18P, and -ADNX

DeviceNet Power Specifications
Power Supply

Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class

2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to
power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60V dc under normal
conditions and under single fault conditions. A PELV supply has the same rating and is
connected to protected earth.

Input Voltage Rating

24V dc nominal

DeviceNet Input Voltage Range

11-25V dc DeviceNet specification

Input Overvoltage Protection

Reverse polarity protected

DeviceNet Power Requirements

24V dc (+4% = 25V dc) @ 30 mA maximum

Power Supply Specifications
Power Supply

Note: In order to comply with CE Low Voltage Directives (LVD), you must use either a NEC Class
2, a Safety Extra Low Voltage (SELV) or a Protected Extra Low Voltage (PELV) power supply to
power this adapter. A SELV supply cannot exceed 30V rms, 42.4V peak or 60V dc under normal
conditions and under single fault conditions. A PELV supply has the same rating and is
connected to protected earth.

Input Voltage Rating

24V dc

10-28.8V dc range

Input Overvoltage Protection

Reverse polarity protected

Inrush Current

6 A maximum for 10 ms

PointBus Output Current

1 A maximum @ 5V dc +5% (4.75-5.25)

Field Side Power Requirements, Maximum 24V dc (+20% = 28.8V dc) @ 400 mA

Interruption

Output voltage will stay within specifications when input drops out for 10 ms at 10V with
maximum load

General Specifications

LED Indicators

1 green/red Adapter status

1 green/red DeviceNet status

1 green/red PointBus status

1 green System Power (PointBus 5V power)

1 green Adapter Power (24V from field supply)

Power Consumption, Maximum

8.1 W @ 28.8V dc

Power Dissipation, Maximum

2.8 W @ 28.8V dc

Thermal Dissipation, Maximum

9.5 BTU/hr. @ 28.8V dc

Isolation Voltage

(continuous-voltage withstand rating)

50V rms

Tested at 1250V ac rms for 60 s

Field Power Bus

Nominal Voltage

Supply Voltage

Supply Current


24V dc

10-28.8V dc range

10 A maximum

Dimensions Inches) (Millimeters)

4.41 H x 2.83 W x 2.56 D (112 H x 72 W x 65 D)

Operating Temperature

IEC 60068-2-1 (Test Ad, Operating Cold),

IEC 60068-2-2 (Test Bd, Operating Dry Heat),

IEC 60068-2-14 (Test Nb, Operating Thermal Shock):

20 to 60°C (68 to 140°F)

Storage Temperature

IEC 60068-2-1 (Test Ab, Un-packaged Non-operating Cold),

IEC 60068-2-2 (Test Bb, Un-packaged Non-operating Dry Heat),

-40 to 85°C (-40 to 185°F)