Publication 1738-UM001A-EN-P - February 2005

Install the ArmorPoint DeviceNet Adapters 1-3

The rotary switches are read periodically. If the switches have been
changed since the last time they were read and they no longer match
the on line address, a minor fault will occur, which is indicated by a
flashing red Adapter Status LED. Settings of 64 through 99 cause the
module to use the last valid node address stored internally. For
example, the last setting internally was 40. If a change is made to 68,
and then you power up, the address will default to 40.

The module is equipped with AutoBaud detect. AutoBaud lets the
module read the settings already in use on your DeviceNet network
and automatically adjusts to follow those settings.

Wire the

DeviceNet Adapters

Following are wiring instructions for the ArmorPoint DeviceNet
adapters.

1738-ADN12 and 1738-ADNX

1738-ADN18 and 1738-ADN18P

(view into connector)

Pin 1 - Drain

Pin 2 - +V

Pin 3 - -V

Pin 4 - CAN_High

Pin 5 - CAN_Low

43764

Male In Connector

Female Out Connector (1738-ADN12)

(Subnet Out - 1738-ADNX only)

43763

(view into connector)

Pin 1 - Drain

Pin 2 - +V

Pin 3 - -V

Pin 4 - CAN_High

Pin 5 - CAN_Low

43746

43749

Male In Connector

Female Out Connector

(1738-ADN18P only)