2-22 What Is the ArmorPoint DeviceNet Adapter?

See the I/O Status Word Bit Definitions table for definitions of the first
2 bytes of each I/O message produced by the adapter on DeviceNet.

The first 2 bytes of output data on the DeviceNet network that are sent
to the adapter are reserved as a command word. No bits have
been defined.

I/O Status Word Bit Definitions

Bit

Operating Mode

Operating Mode Description

0

0 = Run mode

1 = Idle mode

Run - The adapter maps output data to
each module on PointBus.

Idle - Output data with zero length is
sent to I/O modules.

Device Failure - One or more of the
devices in the scanlist has failed to
communicate with the adapter.

Communications Failure - The
adapter has entered the BUSOFF state
on the Subnet. Another Subnet device
is configured with the wrong baud rate.

Duplicate Node Address Failure -
There is another node with the same
address (0) as the scanner on the
Subnet and the adapter has failed its

Dup_MAC_ID test.

1

1 = Device failure (at least one
device failed)

2

1 = Communication failure

3

1 = Duplicate node

address failure

4

Reserved

5

Reserved

6

Reserved

7

Reserved

0

Reserved

1

Reserved

2

Reserved

3

Reserved

4

Reserved

5

Reserved

6

Reserved

7

Reserved

Byte 0