Backup Concepts for the PLC-5 System

Chapter 1

1-2

A PLC-5 system configured with 1785-BCM modules provides high speed
backup communication and switchover of the Data Highway Plus and
remote I/O links. In this section we:

show a typical PLC-5 backup configuration
explain how the backup system works
describe the role of the 1785-BCM module (including 1785-BEM

module)

A Typical PLC-5 Backup Configuration

You must use BCM series B, revision C or later if you are using PLC-5/20,
-5/30, -5/40, or -5/60 processors.

A PLC-5 backup system contains two of each of the following hardware
components:

PLC-5 processor module

Processor:

*

Catalog Number:

PLC-5/11 series A, revision B or later

1785-L11B

PLC-5/15 series B, any revision

1785-LT series B

PLC-5/20 series A, revision B or later

1785-L20B

PLC-5/25 any revision

1785-LT2

PLC-5/30 series A, revision C or later

1785-L30B

PLC-5/40 series A, revision F or later

or series B, revision C or later

1785-L40B

PLC-5/60 series A, revision F or later

or series B, revision C or later

1785-L60B

PLC-5/80 series C, revision A or later

1785-L80B

*

Contact your Allen-Bradley Sales Office or your Allen-Bradley distributor

for additional PLC-5 processors that can be configured with the
1785-BCM modules.

1785-BCM

module

1785-BEM module (when applicable)

power

supply

local

chassis

Figure 1.1 shows a typical PLC-5 backup configuration using PLC-5/15
processors and 1785-BCM modules. Figure 1.2 shows a typical PLC-5
backup configuration using PLC-5/40 or PLC-5/60 processors, 1785-BCM
modules, and 1785-BEM modules.

Applying 1785-BCM Backup
Communication Modules to
the PLC-5 Programmable
Controller