Installing Your PLC-5 Backup System

Chapter 3

3-12

Connecting the 1785-BCM Modules

Connect the High Speed Serial Link (HSSL) to establish communication
between the 1785-BCM modules of the primary system and the secondary
system. The cable for these connections can be a maximum of 15 feet. To
do this, connect a 1770-CD or Belden 9463 cable to terminals 1, 2, and 3
on the wiring arm of each 1785-BCM module as shown in Figure 3.6.

Figure 3.6
1785-BCM Module Connections for High-Speed Serial Link

1 7 9 8 0

PLC-5 processor

PLC-5 processor

Connections show default configuration with Channel 1A as Data Highway Plus
and Channel 1B as Remote I/O Scanner.

1785-BCM module

1771-P4S
power supply

1785-BCM module

1771-P4S
power supply

High Speed Serial Link (HSSL)

1770-CD Cable or Belden 9463
(15 feet maximum)

Blue

Shield

Clear

Blue

Shield

Clear

Local I/O Chassis

Local I/O Chassis

ATTENTION: The 1785-BCM series B module communicates
with the 1785-BCM series A module only if switch 1 of the
SW1 switch assembly is set to ON and if SW2 switch assembly
is properly configured.