Sample programs appendix a – Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual
Page 147

Sample Programs
Appendix A
A-29
Table A.C
Data Table Typical Transfer Time Using Method 2 Program
with Minimal Progam Scan (4–9 ms)
Number of Blocks
Being Transferred
Number of Words
Being Transferred
Transfer Time (in ms)
for Series A BCM
(see notes 1 & 2)
Transfer Time (in ms)
for Series B BCM
Fast Transfer Mode
Enabled (see notes 1,
3, & 4)
1
62
170–250
60–80
3
186
200–300
90–120
7
434
350–500
130–180
10
620
350–600
170–230
16
992
400–1000
180–260
5
32
1984
–
320–720
6
64
3968
–
700–1400
7
1
These times do not significantly change with program scan, but as the number of blocks increase
so does program scan.
2
Times were taken using a PLC-5/25 processor.
3
Series B BCM module with fast mode disabled is approximately 50% slower than the times
shown.
4
Times were taken using a PLC-5/40 processor with one channel configured for DH+ and three
channels configured for remote I/O scanner at 230 kbaud.
5
Program scan 12–16 ms.
6
Program scan 20–25 ms.
7
Program scan 30–35 ms.