Chapter 4

4-19

Figure 4.13
Channel 2B Connections Added Between a PLC-5
and a 1785-BEM Module

1771 –P4S
Power Supply

1771 –P4S
Power Supply

1785 –BCM Module

Local I/O Chassis

Local I/O Chassis

1785 –BEM Module

1785 –BCM Module

1785 –BEM Module

19094

See Note

Shield

See Note

Shield

See Note

See Note

Data Highway Plus – connect the signal conductors with Clear, Shield, and Blue insulation to

terminals 1, SH, and 2 of PLC –5/40 or –5/60 processor respectively, as well as to terminals 18, 19, and 20 of
1785 –BEM module.

Remote I/O – connect the signal conductors with Blue, Shield, and Clear insulation to terminals 1, SH, and 2 of

PLC –5/40 or –5/60 processor respectively, as well as to terminals 18, 19, and 20 of 1785 –BEM module.

18

19

20

Wire channel for either Data Highway Plus or Remote I/O.

PLC-5/40, -5/60, -5/80

PLC-5/40, -5/60, -5/80

2.

Connect the other end of the 1770-CD cable to terminals 18, 19, and
20
on the wiring arm of the 1785-BEM module in the same chassis as
shown in Figure 4.13.

3.

Perform steps 1 and 2 for the other PLC-5/40, -5/60, or -5/80
processor and 1785-BEM module.