Installing Your 1785-BEM Module

Chapter 4

4-16

4.

Connect a 1770-CD cable to terminals 9, 10, and 11 on each of the
1785-BEM wiring arms as shown in Figure 4.10.

Figure 4.10
Channel 2A Connections Added Between 1785-BEM Modules

1771 –P4S
Power Supply

1771 –P4S
Power Supply

Local I/O Chassis

Local I/O Chassis

19091

See
Note

Shield

See
Note

Data Highway Plus – connect the signal conductors with Clear, Shield, and Blue insulation to

terminals 9, 10, and 11 of 1785 –BEM modules respectively.

Remote I/O – connect the signal conductors with Blue, Shield, and Clear insulation to terminals 9, 10, and 11 of

1785 –BEM modules respectively.

Channel 2A

Wire channel for either Data Highway Plus or Remote I/O.

1785-BCM module

1785-BEM module

PLC-5/40, -5/60, -5/80

1785-BCM module

1785-BEM module

PLC-5/40, -5/60, -5/80