Operating Your PLC-5 Backup System

Chapter 5

5-10

With 1785-BCM module, 32 input bits are available in the PLC-5 processor
image table. (The 32 output bits in the output image table are unused and
reserved.) These input words are called Auxiliary Diagnostics/Status Words and
they provide further information about the 1785-BCM module and the
1785-BEM backup expansion module in both the primary and secondary
systems. Refer to Figure 5.6.

Figure 5.6
Auxiliary Diagnostics/Status Words

RESERVED

EXTENDED STATUS

Channel 1A
Status

Channel 1B
Status

Channel 2A
Status

2

Channel 2B
Status

2

01

1

07

1

10

1

17

1

1st Word

2nd Word

W1

W2

W1 Bits:
Bits 00 to 07 = Reserved for Block Transfer Communication
Bit 10 = 1785-BCM series A module
Bit 11 = Fast Data Transfer mode
Bit 12 = Reserved
Bit 13 = Reserved

Bit 14 = Reserved
Bit 15 = Reserved
Bit 16 = Switchover Diagnostic
Bit 17 = 1785-BEM module

W2 Bits:
Bits 00 to 07 = 1785-BEM module communication channels status
Bits 10 to 17 = 1785-BCM module communication channels status

1

Note that these bits are in octal format because they correspond to the input image table.

2

Bits 00 to 07 of the second word can be used or not, depending on whether the 1785-BEM module is in
the backup system or not.

11058I

The first word address corresponds to the module slot, that is, the location of the
1785-BCM module in the I/O chassis. The least-significant byte of this word is
reserved to the 1785-BCM module usage and the most-significant byte shows
extended status of the module. Refer to Table 5.C.