Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual

Page 58

Advertising
background image

Installing Your 1785-BEM Module

Chapter 4

4-15

Figure 4.9
Channel 2A Connections Added Between a PLC-5 Processor
and 1785-BEM Module

Local I/O Chassis

Local I/O Chassis

19090

See Note

Shield

See Note

Shield

See Note

See Note

Data Highway Plus

connect the signal conductors with Clear, Shield, and Blue insulation to
terminals 1, SH, and 2 of PLC –5/40 or –5/60 processor respectively, as well as to terminals 12,
13
and 14 of 1785 –BEM module

.

Remote I/O –connect the signal conductors with Blue, Shield, and Clear insulation to terminals 1,

SH, and 2 of

PLC –5/40 or –5/60 processor respectively, as well as to terminals 12, 13, and 14

of 1785 –BEM module.

Wire channel for either Data Highway Plus or Remote I/O.

1785-BCM module

1785-BEM module

1785-BCM module

1785-BEM module

PLC-5/40, -5/60, -5/80

PLC-5/40 or -5/60

1771-P4S
power supply

1771-P4S
power supply

2.

Connect the other end of the 1770-CD cable to terminals 12, 13, and
14
on the wiring arm of the 1785-BEM module in the same chassis as
shown in Figure 4.9.

3.

Perform steps 1 and 2 for the other PLC-5/40 or PLC-5/60 processor
and 1785-BEM module.