8-1

Diagnosing Faults

This chapter describes how to diagnose faults with your PLC-5 backup
system using:

status indicators on the front of the module
bits in the system status word (word 1 of the BTR instruction)

The status indicators on the front panel of your 1785-BCM module
(Figure 8.1) show both the normal and error conditions of your PLC-5
backup system. Table 8.A lists the indicators and what they indicate.

Figure 8.1
1785-BCM Module Status Indicators

17978

Primary
Secondary
Backplane
Serial Communication Link (HSSL)
Fault

Table 8.A
Status Indicators

Indicator

Color of LED

This LED indicates:

PRI

green

when on — the 1785-BCM module belongs to the primary system

SEC

green

when on — the 1785-BCM module belongs to the secondary system

BPLN

green

when blinking — the 1785-BCM module is executing a block transfer
instruction or communicating properly with the I/O chassis backplane

when off — there is no communication between the 1785-BCM
module and the processor

SER

green

when blinking — proper HSSL communication

when off — failure in the HSSL

FLT

red

when on — hardware failure

Chapter Objectives