Operating Your PLC-5 Backup System

Chapter 5

5-11

Table 5.C
Extended Status Bits (W1)

Bit

1

Description

10

1785-BCM series A module; when on, this bit indicates that the other 1785-BCM module is
series A.

11

Fast Data Transfer mode; when on, this bit indicates that the data valid bit is set to 1 (one)
as soon as the secondary module receives a data block. When off, this bit indicates that the
data valid bit is 1 (one) only when the secondary module receives the complete data
segment.

12

Reserved – always 0

13

Reserved – always 0

14

Reserved – always 0

15

Reserved – always 0

16

Switchover Diagnostic; this bit is always off, but if during a switchover condition this bit is
on, it means that the module must be replaced.

17

1785-BEM module; this bit is on when there is a 1785-BEM backup expansion module in
the system.

1

Bits 0 through 7 (least significant byte of W1) are unused and reserved. For W1, bit 0 is the

least-significant bit and bit 17 is the most-significant bit.

The second auxiliary status word address corresponds to the right-most slot of
the first I/O module group in the I/O chassis. This word shows the channel
configurations of the 1785-BCM and 1785-BEM (if any) modules and also
indicates an error condition in any of these channels.

The most-significant byte of this word corresponds to Channels 1A and 1B of
the 1785-BCM module. The least-significant byte corresponds to Channels 2A
and 2B of the 1785-BEM module. Refer to Figure 5.7.

Figure 5.7
Second Auxiliary Diagnostics/Status Word

ЙЙ

ЙЙ

ЙЙ

ЙЙ

ЙЙЙ

ЙЙЙ

ЙЙ

ЙЙ

00

07

10

03

04

13

14

17

W2

Channel 1A

Channel 1B

Channel 2A

Channel 2B

Error Bit

11059I

ЙЙ

ЙЙ

= error bit per channel