Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual

Page 149

Advertising
background image

Reference Information

Appendix B

B-2

Q.

In which slot of the local I/O chassis do I install the 1785-BEM
module?

A.

We recommend that you install the 1785-BEM module in the
right-most slot of the first I/O module group in the I/O chassis for ease
in making connections and programming. Note that the 1785-BEM
module must be in the same I/O group as the 1785-BCM module.
(Refer to Chapter 3 and Chapter 4 for more information.)

Q.

Does the 1785-BEM module have to go next to the 1785-BCM
module?

A.

Yes. They should be placed in the same I/O module group.

Q.

How do I set the local I/O chassis backplane switches for a PLC-5
backup system?

A.

Set the switches as shown in the following table. (Refer to Chapter 3
for more information.)

Set switch(es)

To this position:

1

OFF – to turn off outputs in the chassis when a fault is detected.

2 and 3

both OFF – these switches are not used

4 and 5

1

4 – ON
configure for 1/2-slot addressing*

5 – OFF

configure for 1/2-slot addressing*

6 and 7

as required for your application

8

as required for your application

*

The 1785-BCM module appears to the PLC-5 processor as a 32-point input module. You must

configure switches 4 and 5 for 1/2-slot addressing or 1-slot addressing. If not configured as 1/2-
or 1-slot addressing, a PLC-5 processor fault will occur. If you are installing a 1785-BEM
module, you must select 1/2-slot addressing.

Q.

How do I set the remote I/O chassis backplane switches for a
PLC-5 backup system?

A.

The operation of the PLC-5 backup system is independent of the
operation of the remote I/O chassis; therefore, you can set these
switches as required for your application. For more information about
setting the I/O chassis switches, refer to the PLC-5 Enhanced and
Ethernet Programmable Controllers User Manual (publication
1785-6.5.12).

Advertising