Diagnosing faults chapter 8 – Rockwell Automation 1785-BCM_BEM, D17856.5.4 PLC-5 Backup Communication Module User Manual User Manual

Page 117

Advertising
background image

Diagnosing Faults

Chapter 8

8-7

Figure 8.4
BCM and BEM Modules Configuration Status Word W2
(Auxiliary Diagnostic/Status Word)

17

16

15

14

13

12

11

10

7

6

5

4

3

2

1

0

Channel
A Config

Channel
A Error

Channel
B Config

Channel
B Error

Bits

1

12

11

10

2

1

0

Description

1

1

1

Data Highway Plus network

1

1

0

Remote I/O – adapter mode at 57.6 kbaud

1

0

1

Remote I/O – adapter mode at 115.2 kbaud

1

0

0

Remote I/O – adapter mode at 230.4 kbaud

0

1

1

Relay switch

0

1

0

Remote I/O – scanner mode at 57.6 kbaud

0

0

1

Remote I/O – scanner mode at 115.2 kbaud

0

0

0

Remote I/O – scanner mode at 230.4 kbaud

Bits

1

16

15

14

6

5

4

Description

1

1

1

Data Highway Plus network

1

1

0

Remote I/O – adapter mode at 57.6 kbaud

1

0

1

Remote I/O – adapter mode at 115.2 kbaud

1

0

0

Remote I/O – adapter mode at 230.4 kbaud

0

1

1

Relay switch

0

1

0

Remote I/O – scanner mode at 57.6 kbaud

0

0

1

Remote I/O – scanner mode at 115.2 kbaud

0

0

0

Remote I/O – scanner mode at 230.4 kbaud

Bits

1

13

3

Description

0

0

Normal operation

1

0

Channel 1B error

0

1

Channel 2B error

1

1

Channels 1B and 2B error

Bits

1

17

7

Description

0

0

Normal operation

1

0

Channel 1A error

0

1

Channel 2A error

1

1

Channels 1A and 2A error

1

Bit conditions: 1 = ON, 0 = OFF

Advertising